modular type air cooled water chiller

60kw Modular type Air Cooled water Chiller R407C/Modular chiller

Model AC+LFQW(R)F60M
Brand AC+
Unit set
Min order 1
Supply ability 1000 sets per month
Payment 50% T/T as deposit rest before delivery
Port Tianjin
Certification ISO 9000/14001/18001
Place China
Packaging Export Standard Package
Send Inquiry

MODULAR TYPE AIR COOLED WATER CHILLER FEATURES

1.60 Modular chiller The master module can work independently or together with up to 7 slave modules, capacity from 63 to 504kW.

2. Air cooled modular units with V type heat exchanger: panels, frame and base are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.

3.Air cooled water chiller 3-phase scroll type compressor, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.

4.External rotor type axial fans, equipped with three phase direct drive motors, low noise 8 poles, protection level IP54, provided with a protective outlet grille.

5.Evaporator built with high efficiency tube in tube type heat exchanger, factory insulated with flexible close cell material.

6.Condenser built with seamless copper tubes mechanically expanded into blue hydrophilic aluminum fins.

  

 

7. R407C scroll modular chiller Refrigerant circuit complete with charge valves, filter drier, sight glass, gas-liquid separator, thermostatic expansion valve, high & low pressure switch. The heat pump unit is completed also with 4-way valve, liquid receiver and one way valve.

8. Hydraulic circuit built with galvanized pipe, complete with water discharge connection for tube in tube heat exchanger and flange type hydraulic connectors in two directions easy for connections from both sides of the units.

9. Packaged modular chiller Electric panel consist of: compressor contactor, fan motor contactor, compressor protection breaker, fan protection breaker, phase sequence relay and microprocessor with function display (display only for master/packaged unit)

10.Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.

OPTIONAL

¨ Paddle flow switch;

¨ Metallic filter for hydraulic circuit;

¨ Water pump;

¨ Rubber antivibration mounting.

¨ Heat recovery functions

NOMENCLATURE

AC+LS  QW  R  F  C  60  U  M

 1          2   3  4   5   6   7   8




1.Water chiller
2.Hermetic scroll compressor
3.Unit type:
   R : heat pump
  -- : cooling only 
4.Air cooled   
5.Refrigerant type
 --: R22
  A: R410a
  B: R290 
  C: R407c
6.Size

7.Finned heat exchanger type
    V: V type coil
8.Module type
    M: master module
    S: slave module
    P: packaged type


TECHNICAL DATA

* Ambient temperature 35ºC; evaporator water in/out 12/7 ºC;

** Ambient temperature DB 7 ºC, WB 6 ºC; condenser water in/out temperature 40/45 ºC;

*** In the nominal water flow condition the pressure drop is between this range.

**** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.

modular chiller

OVERALL DIMENSIONS

AC+LSQW(R)FC60V


Modular Type Air Cooled Water Chiller/Modular Chiller 17ton-147ton R407C Air Cooled Scroll Chiller

AC+LFQW(R)F60M

Cooling capacity: 63÷504 kW

Heating capacity: 68÷544 kW