Modular Water Source Heat Pump 25ton/37ton/45ton modular heat pump
Model | AC+GSHP 90K ÷ 160K |
Brand | AC+ |
Unit | set |
Min order | 1 |
Supply ability | 1000 sets per month |
Payment | 50% T/T as deposit rest before delivery |
Port | Tianjin |
Certification | ISO 9001/14001/18001 |
Place | China |
Packaging | Export Standard Package |
FEATURES
90/130/160 modular water heat pump The master module can work independently or together with up to 7 slave modules, flexible design, stable performance, easy maintenance.
Reusable: using solar energy stored in earth as cooling & heating source.
Panels and frame are made from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
Water source modular heat pump 3-phase scroll type compressor, with built-in thermal overload cut-out and crankcase heater, mounted on rubber vibration dampers.
Scroll water heat pump Shall and tube type evaporator, factory insulated with flexible close cell material.
Shall and tube dry expansion type condenser, factory insulated with flexible close cell material.
R22 modular heat pump The refrigerant circuit is complete with filter drier, direct expansion valve, high and low pressure switch.
Packaged water heat pump Acting as multi-function unit such as cooling, heating, with heat recovery function producing hot water for domestic use.
LCD display as standard
Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.
Wide application as hotel, apartment, villa, factory, shopping center, office building, school, etc.
ELECTRIC PANEL
consists of:
l Compressor breaker,
l Compressor contactor
l Phase sequence relay
l Control circuit breaker
l Microprocessor with function display
OPTIONAL
l Heat recovery as optional
l Electronic controller with BMS system.
NOMENCLATURE
AC+GSHP 90 K C H T Z D | ||
Water source heat pump Model Ž K: Modular unit Refrigerant type --: R22 C: R407c B: R134a | Heat Recovery: --: standard unit H: partial heat recovery Q: total heat recovery ‘ Heat exchanger type: --: shell-tube T: tube in tube | Module type Z: master module --: slave module “ Project condition D: Underground water loops --: Underground water |
TECHNICAL DATA
Performance values refer to the following conditions:
* Source side water inlet/outlet temperature 18ºC/29ºC, user side water inlet/outlet temperature 12ºC/7ºC, for Underground water
Source side water inlet/outlet temperature 25ºC/30ºC, user side water inlet/outlet temperature 12ºC/7ºC, for Underground water loops
** Source side water inlet/outlet temperature 15ºC/8ºC, user side water inlet/outlet temperature 40ºC/45ºC, for Underground water
Source side water inlet/outlet temperature 8ºC/4ºC, user side water inlet/outlet temperature 40ºC/45ºC, for Underground water loops
*** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a dear field.
OVERALL DIMENSIONS
| GSHP90K-D | GSHP130K-D | GSHP160K-D | GSHP90K | GSHP130K | GSHP160K |
A | 2200 | 2200 | 2735 | 2200 | 2200 | 2735 |
B | 1630 | 1630 | 2180 | 1630 | 1630 | 2180 |
D | 940 | 985 | 985 | 930 | 985 | 985 |
E | 1380 | 1380 | 1400 | 1380 | 1380 | 1400 |
F | 480 | 480 | 560 | 480 | 480 | 560 |
G | 1290 | 1290 | 1760 | 1290 | 1290 | 1760 |
H | 380 | 380 | 460 | 380 | 380 | 460 |
GSHP90KH-D | GSHP130KH-D | GSHP160KH-D | GSHP90KH | GSHP130KH | GSHP160KH | |
A | 2300 | 2300 | 2835 | 2300 | 2300 | 2835 |
B | 1630 | 1630 | 2180 | 1630 | 1630 | 2180 |
D | 940 | 985 | 985 | 940 | 985 | 985 |
E | 1380 | 1380 | 1400 | 1380 | 1380 | 1400 |
F | 480 | 480 | 560 | 480 | 480 | 560 |
G | 1290 | 1290 | 1760 | 1290 | 1290 | 1760 |
H | 380 | 380 | 460 | 380 | 380 | 460 |
K | 375 | 375 | 385 | 375 | 375 | 385 |
Modular
Water Source Heat Pump/Water Modular Heat Pump 25ton/37ton/45ton
AC+GSHP 90K ÷ 160K
Cooling
capacity: 90 ÷ 160 kW
Heating capacity: 82 ÷ 168 kW